| Product Name | Fiplex DH7S-A-733AH - DIGITAL SIGNAL BOOSTER. PS 700 MHz, High Capacity Single Band +33dBm, Class A, 64 filters, NFPA, AC. | Comba Public Safety 27dBm Class A Dual Band 700/800MHz BDA (AC/DC) | Comba Public Safety 33dBm Class B Dual Band 800MHz BDA (AC/DC) | VHF / UHF / 700 / 800 Quad band | ProtectLink Class A Software definable ERCES system |
|---|---|---|---|---|---|
| Brand |
|
|
|
|
|
| Supported Bands | 700 | 700/800 Dual-Band | 800 | VHF/UHF Dual-Band | 700 , 800 , 700/800 Dual-Band , Band 14 |
| Class | A | A | B | A | A |
| Uplink Frequencies in MHz From | 788 | 138 | 788 | ||
| Uplink Frequencies in MHz To | 805 | 824 | 824 | ||
| Uplink Frequencies in MHz | From: 788 MHz To: 805 MHz | From: MHz To: MHz | From: MHz To: MHz | From: 138 MHz To: 824 MHz | From: 788 MHz To: 824 MHz |
| Downlink Frequencies in MHz From | 758 | 138 | 758/851 | ||
| Downlink Frequencies in MHz To | 775 | 869 | 776/869 | ||
| Downlink Frequencies in MHz | From: 758 MHz To: 775 MHz | From: MHz To: MHz | From: MHz To: MHz | From: 138 MHz To: 869 MHz | From: 758/851 MHz To: 776/869 MHz |
| Uplink Composite Power in dBm | 24 dBm | 30 dBm | 27 dBm | ||
| Downlink Composite Power in dBm | 33 dBm | 33 dBm | 34 dBm | ||
| Power Consumption in Watts | 80 Watts | 60 Watts | 130 Watts | ||
| 2524 NRTL for Listed Products | SGS | SGS | SGS | MET | INTERTEK/ETL |
| 2524 Listing Status | Listed | Listed | Listed | In NRTL Lab / Pending | Listed |
| 2524 Certification Date | |||||
| STD 2524 Comments | UL62368 / 60957 | Systems consists of one ProtectLink BDA (available currently in 5 models) plus CS19-BBC-003 battery cabinet with UL Recognized sealed lead acid batteries and CS40-ANNUNC remote annunciation panel. | |||
| Other Certifications | FCC, NFPA, Buy American Compliant | UL 60950-1 & UL 60950-22 Compliant | UL 60950-1 & UL 60950-22 Compliant | UL 62368 Certified, FCC Certified, NFPA & IFC Compliant |
UL 62368-1, Communications Technology Equipment. UL508A (UL50E NEMA Type 4). FCC ID NVRDPSA81090-78 Canada ISED 4307A-DPSA810907 |
| Website Link or Product Page | https://fiplex.com/flex-in-building-solution/ | Safe-Com Wireless Product Download Page | Westell ProtectLink 700/800MHz class A/B BDAs | ||
| Notes | www.fiplex.com | Multi-band capable, Dual Class A & B in one unit, NFPA compliant, Interlaced frequencies, Simplex, BBU available | Westell ProtectLink Public Safety BDAs represent the next revolution in DAS design, offering the most flexible platform available on the market. Available in 5 models, 2.5W or 1W, single or dual band. | ||
| Organization Name | Honeywell-Fiplex | Comba Telecom, Inc. | Comba Telecom, Inc. | Rath by Avire | Westell Technologies |