Bi-Directional Amplifier (BDA) Comparison Chart

Step 1) Please select the frequencies needed to be rebroadcasted. Per NFPA 1221 version 2019;
Step 2) Then select the Class type.
Step 4) Filter by 2524 Listing Status (optional).
Step 5) Official Certifications from NRTL Only (optional).
Product Name Guardian A TruePath - Channelized (Class A) 700 or 800 MHz Public Safety BDA, 2 Watts, DC Fiplex DH7S-A-733A - DIGITAL SIGNAL BOOSTER. PS 700 MHz + FirstNet, Single Band +33dBm, 32 filters + 2 Adj sub band, NFPA, AC. TruePath - Channelized (Class A) 700 and 800 MHz Publics Safety BDA, 1/2 Watt, DC TruePath - Class B 700 or 800 MHz Public Safety BDA, 1/2 Watt, AC
Supported Bands 700/800 Dual-Band , Band 14 700 , 800 , Band 14 700 700/800 Dual-Band , Band 14 700 , 800 , Band 14
Class A A A A B
Uplink Frequencies in MHz From 788 788 788 788 788
Uplink Frequencies in MHz To 816 824 805 824 824
Uplink Frequencies in MHz From: 788 MHz To: 816 MHz From: 788 MHz To: 824 MHz From: 788 MHz To: 805 MHz From: 788 MHz To: 824 MHz From: 788 MHz To: 824 MHz
Downlink Frequencies in MHz From 758 758 758 758 758
Downlink Frequencies in MHz To 861 896 775 896 896
Downlink Frequencies in MHz From: 758 MHz To: 861 MHz From: 758 MHz To: 896 MHz From: 758 MHz To: 775 MHz From: 758 MHz To: 896 MHz From: 758 MHz To: 896 MHz
Uplink Composite Power in dBm 27 dBm 27 dBm 24 dBm 27 dBm 27 dBm
Downlink Composite Power in dBm 33 dBm 33 dBm 33 dBm 27 dBm 27 dBm
Power Consumption in Watts 160 Watts 80 Watts 160 Watts
2524 NRTL for Listed Products No NRTL Reported UL SGS UL UL
2524 Listing Status Listed Listed Listed Listed Listed
2524 Certification Date
STD 2524 Comments Investigated to UL2524 - 2nd Edition Revised 2019-02-28, Bi-directional amplifier Investigated to UL2524 - 2nd Edition Revised 2019-02-28, Bi-directional amplifier Investigated to UL2524 - 2nd Edition Revised 2019-02-28, Bi-directional amplifier
Other Certifications CAN/CSA-C22.2 No. 62638-1, FCC Part 20 Part 90 FCC, NFPA, Buy American Compliant CAN/CSA-22.2 No. 62638-1, FCC Part 20 Part 90 CAN/CSA-C22.2 No. 62638-1, FCC Part 20 Part 90
Website Link or Product Page https://toweriq.nyc/guardian-series 7831758-002 https://fiplex.com/flex-in-building-solution/ 7831758-0023 7831851-0012
Notes Wireless Supply also offers our BDA products as a kit which includes the BBU, annunciator, and alarm panel junction boxes for connection to a buildings fire alarm panel www.fiplex.com Wireless Supply also offers our BDA products as a kit which includes the BBU, annunciator, and alarm junction boxes for connection to a buildings fire alarm panel Wireless Supply also offers our BDA products as a kit which includes the BBU, annunciator, and alarm junction boxes for connection to a buildings fire alarm panel
Organization Name Potter ERCES Wireless Supply, LLC Honeywell-Fiplex Wireless Supply, LLC Wireless Supply, LLC